Flue Gas Cooling----Application of Air Heat Exchanger
Author:sehenstar  Source:本站  Pubtime:2017-06-22 10:07:31  Click:567

One day we received an inquiry from our customer:


flue gas :                                                        
- temperature 120 degC                                    

- Flow : 800.000 Nm3/H                     

- Static Pressure : 102 mBar     

    

Q  =  V * C (TF –TA)

Q = Heat content of flue gas                        

V = Actual flue gas flow                                                 

C= Specific heat of flue gas                                 

TF = TEMPERATURE FLUE GAS                    

TA=TEMPERATURE AMBIENT                        

Temperature flue gas 120 degC - C = 0.2577 Kcal / kg. ̊ C
Q  =  V * C (TF –TA)
Q = 800,000 Nm3/h  *  0.2577 Kcal / kg. ÌŠ C ( 120 ÌŠ C  -  35 ÌŠ C )= 17,523,600 Kcal/h

REFRIGERANG = R245fa                                    

REFRIGERANT INLET TEMPERATURE : 40 DEGREE C                           
REFRIGERANT OUTLET TEMPERATURE : 90 DEGREE C                        
FLOW RATE : 16.5 TON/HOUR                                                          

FLUE GAS COMES FROM KILN COAL FIRE , C = 0.2577 Kcal / kg. ÌŠ C    


Our engineer made the following proposal with the remarks:

It is based on flue gas flow of 200,000 m3 / h, the absolute pressure of R245 fa of 16 bar.